Wet-bulb temperature is the one property on this site that can't be solved with a simple formula plugged straight in — it has to be searched for. Here's exactly how the calculator does it, and how the number relates to an actual field measurement.
Wet-bulb temperature Twb is defined implicitly by the psychrometer equation:
es(Twb) − 0.000662 × P × (Tdb − Twb) = e
where e is the actual (known) vapor pressure, P is barometric pressure in kPa, and es(Twb) is the Tetens saturation formula evaluated at the unknown Twb. Twb appears on both sides of this equation — once inside the exponential saturation function and once in the linear correction term — so there's no way to algebraically isolate it. The calculator solves it numerically by bisection: it picks a bracketing range of candidate wet-bulb temperatures, repeatedly narrows the range in half by checking which side the equation's residual is closer to zero on, and converges on the answer in a handful of iterations.
At Tdb = 25°C, 50% RH, sea-level pressure: known vapor pressure e = 0.5 × es(25) = 0.5 × 3.17 = 1.58 kPa. Solving the psychrometer equation for this case gives Twb ≈ 18.0°C — the same value you'd read off a standard ASHRAE psychrometric chart at that dry-bulb/RH intersection, which is a good sanity check that the bisection solver and a printed chart agree.
In the field, wet-bulb temperature isn't calculated — it's measured directly with a sling psychrometer: two identical thermometers mounted side by side, one left dry (the dry-bulb reading) and one with a wetted cotton wick slipped over its bulb. Spinning the assembly (or using a battery-powered aspirated version) for 60–90 seconds drives air across the wet wick, evaporating water and cooling that thermometer below the dry-bulb reading. The cooling stops once the air right at the wick's surface is fully saturated — that equilibrium reading is the wet-bulb temperature, and the physics of that evaporative equilibrium is exactly what the psychrometer equation above models mathematically.
Technique matters: insufficient airflow across the wick, a dirty or mineral-caked wick, or using water that isn't close to the air's own temperature can all introduce a degree or more of error. A well-maintained aspirated psychrometer is accurate to roughly ±0.2–0.3°C; a casually used sling version is more commonly ±0.5°C or so in practiced hands.
For any air that isn't already saturated, wet-bulb temperature always falls strictly between dew point and dry-bulb temperature: Tdp ≤ Twb ≤ Tdb. At 100% RH all three are equal. See the dew point vs. wet-bulb page for a worked comparison table across several humidity levels at the same dry-bulb temperature.